Do garages in flood zones need flood vents?
When a garage below the base flood elevation needs flood openings, how many, how much net open area, how high above grade, and why a garage door doesn't count.
On this page: 5 sections
- 1Do attached garages below the base flood elevation need flood openings?
- 2How many flood openings does a garage need, and how much open area?
- 3How high above grade can the bottom of a flood vent sit?
- 4Does a garage door count as a flood vent?
- 5What rules apply to a wet-floodproofed accessory structure used for parking?
Yes, when the garage floor is below the base flood elevation (BFE): openings are required in the exterior walls of an attached garage, at least two of them, with a total net area of at least one square inch for every square foot of enclosed area and bottoms no higher than one foot above grade.1
Do attached garages below the base flood elevation need flood openings?
Flood vents are specialized openings designed to allow the free flow of water in and out of enclosed areas during a flood event.2 Under the August 2008 edition of NFIP Technical Bulletin 1, openings are required in the exterior walls of an attached garage whose floor is below the BFE, and the use of the garage space must be limited to parking of vehicles, building access and storage. An attached garage built with its floor below the BFE and without compliant openings has a consequence in the bulletin: the garage floor becomes the lowest floor.1
The federal rule behind the bulletin is 44 CFR 60.3(c)(5), which applies to all new construction and substantial improvements and requires fully enclosed areas below the lowest floor that are usable solely for parking of vehicles, building access or storage to be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters.3 Community or State requirements that exceed those of the NFIP take precedence.1
How many flood openings does a garage need, and how much open area?
Under 44 CFR 60.3(c)(5), a design must either be certified by a registered professional engineer or architect or provide a minimum of two openings with a total net area of not less than one square inch for every square foot of enclosed area subject to flooding.3 Each enclosed area is required to have a minimum of two openings on exterior walls, and the openings should be installed on at least two sides of each enclosed area.1 In Carteret County's guide, the square footage of an enclosed area is measured from the outside of the walls, and each enclosed area is required to have a minimum of two flood openings on different walls.3
Openings that are entirely above the BFE, or any portion of an opening that is above the BFE, are not counted towards compliance with the flood opening requirements.1 Openings in interior walls are not counted toward the required total opening requirement based on the exterior measurement of the enclosed area. To maintain safe fire separation, flood openings should not be placed in the wall separating a garage from living spaces and crawlspaces unless the devices used as flood openings are designed to satisfy fire-separation requirements.4
The table sets the three figures side by side as each page prints them:
| Requirement | Figure | Where the figure is printed |
|---|---|---|
| Number of openings | A minimum of two openings on exterior walls for each enclosed area | 1 |
| Net open area | 1 square inch of net free area for every 1 square foot of enclosed area, where non-engineered openings are used | 3 |
| Height above grade | The bottom of each flood opening no higher than 1 foot above the higher of the final interior or exterior grade | 4 |
How high above grade can the bottom of a flood vent sit?
The bottom of each opening is to be located no higher than 1 foot above the grade that is immediately under each opening. The 1 foot limit serves the expectation that the difference in water levels between the interior and exterior will not exceed 1 foot as water begins to rise and as floodwaters recede from the site. Where the interior and exterior grades differ, the higher of the final interior grade and the finished exterior grade immediately under each opening is used.1
The March 2020 edition of the bulletin states the same limit: the bottom of each flood opening must be positioned no higher than 1 foot above the higher of the final interior or exterior grade. An enclosure that is below grade on all sides is a basement, and basements do not comply with the minimum NFIP requirements.4 Carteret County's guide adds that flood openings must be below the BFE to perform their intended function.3
Does a garage door count as a flood vent?
No: human intervention would be necessary to open garage doors when flooding is expected, which is inconsistent with the requirement that openings allow for the automatic entry and exit of floodwaters. Gaps that may be present between the garage door and the door jamb or walls do not guarantee automatic entry and exit of floodwaters and do not count towards the net open area requirement. Openings may, however, be installed in exit doors and garage doors.1
Carteret County's guide says the same of windows, entry doors and garage doors: none is an acceptable flood opening. The residential code section R322.2.2.1 reprinted in the Carteret County guide permits openings to be installed in doors and windows, and doors and windows without installed openings do not meet the section's requirements. Human intervention is not acceptable to activate a flood opening, so any air ventilation device that can be closed manually must be permanently disabled in the open position.3
What rules apply to a wet-floodproofed accessory structure used for parking?
The March 2020 edition of NFIP Technical Bulletin 1 lists measures a wet-floodproofed accessory structure must comply with, including use limited to parking of vehicles and storage, flood damage-resistant materials below the BFE, and anchoring to resist flotation, collapse or lateral movement under flood conditions. An accessory structure that is allowed to be wet floodproofed must not be used for any habitable or other prohibited purpose.4
In Key West, wet floodproofing is permitted for non-habitable structures below the base flood elevation for minimal storage, building access or parking. The primary purpose of flood vents is to equalize hydrostatic pressure on both sides of a building's foundation walls, which reduces the risk of structural damage caused by the buoyancy force of floodwaters.2
NFIP Technical Bulletin 1 as Charlestown, Rhode Island and the City of Norfolk publish it, Carteret County's flood opening guide and the City of Key West's wet floodproofing page, checked November 2026.
Sources (4)
- NFIP Technical Bulletin 1 (August 2008, Charlestown, Rhode Island's copy): Openings in Foundation Walls and Walls of Enclosures, read November 25, 2026 ↑
- City of Key West: Wet Floodproofing, read November 25, 2026 ↑
- Carteret County, North Carolina: Non-Engineered Opening Guide, January 2015, read November 25, 2026 ↑
- NFIP Technical Bulletin 1 (March 2020, City of Norfolk's copy): section 8, Requirements and Guidance for Installation of Flood Openings, read November 25, 2026 ↑